Number of inputs and outputs- Number of digital outputs: 2
Measuring range - 0...100 bar 0...1450 psi 0...10 MPa
Process connection- threaded connection G 1/4 internal thread
Application:-
Special feature- Gold-plated contacts
Measuring element- ceramic-capacitive pressure measuring cell
Application- for industrial applications
Media- Liquids
Conditionally suitable for- use in gases at pressures > 25 bar only on request
Medium temperature[°C]- -25...80
Type of pressure- relative pressure
Electrical Data:-
Operating voltage[V]- 18...30 DC; (to SELV/PELV)
Current consumption[mA]- < 35
Min. insulation resistance[MΩ]- 100; (500 V DC)
Protection class- III
Reverse polarity protection- yes
Power-on delay time[s]- < 0.3
Integrated watchdog- yes
Number of inputs and outputs- Number of digital outputs: 2
Outputs:-
Total number of outputs- 2
Output signal- switching signal; IO-Link; (configurable)
Electrical design- PNP/NPN
Number of digital outputs- 2
Output function- normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC[V]- 2.5
Permanent current rating of switching output DC[mA]- 150; (200 (...60 °C) 250 (...40 °C))
Switching frequency DC[Hz]- < 170
Short-circuit protection- yes
Type of short-circuit protection- pulsed
Overload protection- yes
Interfaces:
Communication interface- IO-Link
Transmission type- COM2 (38,4 kBaud)
IO-Link revision- 1.1
SDCI standard- IEC 61131-9
SIO mode- yes
Required master port type- A; (when pin 2 not connected: B)
Process data analogue- 1
Process data binary- 2
| storage_Type | No |
|---|---|
| Manufacturer Part No | PN7092 |
| Manufacturer | No |
| Datasheet | No |
Products Questions:
There are no product questions yet.
Please login in to your account to place a question